Digital Ac Output Modules - Rockwell Automation POINTBlock Series User Manual

I/o digital and analog modules
Table of Contents

Advertisement

102
POINT I/O Module Data
Publication 1734-UM001D-EN-P - April 2008
Default Data Map for the 1734-OB2EP Output Module
Message Size: 1 Byte
7
6
5
Produces
(scanner Rx)
Where:
0 = no error, 1 = error
Message Size: 1 Byte
7
6
5
Consumes
(scanner Tx)
Where:
0 = Off, 1 = On

Digital ac Output Modules

T
he 1734-OA2 ac output module features include the following:
• 120V ac outputs with a range of 74...264V ac (120/220V ac nominal)
• Each output is rated at 0.10 A minimum to 0.75 A maximum
• Autobaud (will match baud of existing devices on the network)
• Sequential auto addressing
Default Data Map for the 1734-OA2 Output Module
7
Produces (scanner Rx)
Consumes (scanner Tx)
Where:
0 = Off, 1 = On
Default Data Map for 1734-OA4 Modules
Produces (scanner Rx)
Consumes (scanner Tx)
Where: 0 = Off, 1 = On
4
3
2
1
Not used
Ch1
4
3
2
1
Not used
Ch1
6
5
4
3
2
1
No produced data
Not used
Ch1
7
6
5
4
3
2
No produced data
Not used
Ch 3 Ch 2
0
Ch0
Channel status
0
Ch0
Channel state
0
Ch0
Channel state
1
0
Ch1 Ch0 Channel state

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents