Indication
Probable Cause
Module Status
Off
No power applied to device.
Solid green
Device is operating normally.
Flashing green
Device needs commissioning due to configuration
missing, incomplete, or incorrect.
Flashing red
Recoverable fault is present.
Device did not pass internal test.
Solid red
Unrecoverable fault may require device replacement.
Flashing red/green
Device is in self-test.
Network Status
Off
Device is not online.
- Device has not completed Auto Baud detection
because there is no network traffic.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator.
Flashing green
Device is online but has no connections in the
established state.
Solid green
Device is online and has connections in the established
state.
Flashing red
One or more I/O connections are in timed-out state.
Solid red
Critical link failure is present with failed communication
device. Device detected error that prevents it from
communicating on the network.
Flashing red/green
Communication faulted device - the device has detected
a network access error and is in communication faulted
state. Device has received and accepted an Identify
Communication Faulted Request - long protocol
message.
Troubleshoot with the Indicators
Recommended Action
Apply power to device.
None.
Configure device properly.
1. Cycle power to device.
2. If condition persists, replace device.
Replace device.
None.
Apply power to device, wait for MAC_id to complete,
and correct, as needed.
None - device is in Idle or Program mode.
None.
Check for I/O module failure, and correct, as needed.
Verify that adapter and terminal bases are properly
installed, and reinstall, as needed.
Verify that adapter is properly installed, and reinstall, as
needed.
Publication 1734-UM001D-EN-P - April 2008
143