1734-Ox2 Relay Output Module; Analog Module Default Data Maps; 1734-Ie2C Analog Current Input Module - Rockwell Automation POINTBlock Series User Manual

I/o digital and analog modules
Table of Contents

Advertisement

174
Default Data Maps
Consumes (scanner Tx)
Where: 0 = NO contact Off, NC contact On
Analog Module Default
Data Maps
Produces (scanner Rx)
Consumes (scanner Tx)
Where:CF = Channel Fault status0 = no error1 = fault
CM = Calibration Mode
0 = normal1 = calibration mode
LA = Low Alarm 0 = no error1 = fault
HA = High Alarm
0 = no error1 = fault
LLA = Low/Low Alarm 0 = no error1 = fault
HHA = High/High Alarm
0 = no error1 = fault
UN = Underrange 0 = no error1 = fault
OR = Overrange
0 = no error1 = fault
Channel Status Bytes
Bit 7
Bit 6
Over Range Under Range High High Alarm
Publication 1734-UM001D-EN-P - April 2008

1734-OX2 Relay Output Module

Message Size: 1 Byte
1 = NO contact On, NC contact Off
I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. You map these messages into the processor memory.

1734-IE2C Analog Current Input Module

Message Size: 6 Bytes
15
14
13
12
11
Input Channel 0 High Byte
Input Channel 1 High Byte
Status Byte for Channel 1
OR
UR
HHA
LLA HA
No consumed data
Channel Status
Bit 5
Bit 4
Low Low Alarm
7
6
5
4
3
Not used
10
09
08
07
06
Input Channel 0 Low Byte
Input Channel 1 Low Byte
Status Byte for Channel 0
LA
CM
CF
OR
UR
Bit 3
Bit 2
High Alarm
Low Alarm
2
1
0
Ch1
Ch0
Channel state
05
04
03
02
01
HHA
LLA HA
LA
CM
Bit 1
Bit 0
CAL Mode
Channel Fault
00
CF