Rockwell Automation POINTBlock Series User Manual page 137

I/o digital and analog modules
Table of Contents

Advertisement

10. Click the Download to Device button.
The status indicator for the channel being calibrated blinks.
11. Set the voltage source to +10.0V.
12. Click Accept High Calibration.
13. Click the Download to Device button.
Calibration is complete as soon as High and Low calibration for the
selected channels are done successfully.
14. Repeat these steps to calibrate the other channel, if desired.
Both high and low inputs must be accepted in order for the module to
finish calibration.
Calibration is now complete. If the module does not accept calibration
(status indicator is still blinking), from the Device Parameters dialog,
click Abort Calibration and start over.
Calibrate Your Analog Modules
Publication 1734-UM001D-EN-P - April 2008
135