POINT I/O Module Data
Default Data Map for the 1734-IE2V Analog Input Module
Produces (scanner Rx)
Consumes (scanner Tx)
Where: CF = Channel Fault status; 0 = no error, 1 = fault
LA = Low Alarm; 0 = no error, 1 = fault
LLA = Low/Low Alarm; 0 = no error, 1 = fault
UR = Underrange; 0 = no error, 1 = fault
Publication 1734-UM001D-EN-P - April 2008
Input Channel 0 - High Byte
Input Channel 1 - High Byte
Status Byte for Channel 1
OR
UR
HHA LLA
HA
No consumed data
Input Channel 0 - Low Byte
Input Channel 1 - Low Byte
Status Byte for Channel 0
LA
CM
CF
OR
UR
CM = Calibration Mode; 0 = normal, 1 = calibration mode
HA = High Alarm; 0 = no error, 1 = fault
HHA = High/High Alarm; 0 = no error, 1 = fault
OR = Overrange; 0 = no error, 1 = fault
HHA
LLA
HA
LA
CM
CF