Rockwell Automation POINTBlock Series User Manual page 165

I/o digital and analog modules
Table of Contents

Advertisement

Indication
Probable Cause
Network Activity
Off
No link established.
Flashing
Transmit or receive activity present.
green/Off
Steady green
Link established.
Network Status
Off
Device not initialized. The module does not have an IP address.
Flashing green
No CIP connections present. Device has an IP address, but no CIP
connections are established.
Solid green
CIP connections present. Device online and has an IP address, and CIP
connections are established.
Flashing red
One or more CIP connections has timed-out.
Solid red
Duplicate IP address detected.
Flashing
The module is performing a self-test (only occurs during power cycle
red/green
test).
Troubleshoot with the Indicators
Recommended Action
Verify network cabling, and correct, as
needed.
None.
None.
Apply power to device, verify IP address,
and correct, as needed.
None.
None.
Check for I/O module failure and controller
operation, and correct, as needed.
Verify IP address setting and correct, as
needed.
None.
Publication 1734-UM001D-EN-P - April 2008