Rockwell Automation POINTBlock Series User Manual page 163

I/o digital and analog modules
Table of Contents

Advertisement

Indication
Probable Cause
POINTBus Status
• No power supplied.
Off
• Hardware check is in progress.
• Initialization is in progress.
Solid green
Normal operation present.
Flashing red
1 Hz - Incorrect POINT I/O module installed.
POINT I/O module removed from backplane.
Solid red
Critical link failure (BUS_OFF) is present.
Indicator
Indication
System Power
Off
Green
Field Power
Off
Green
Probable Cause
System power not applied.
System power (5V) present
Field power not applied.
Field power (24V) applied.
Troubleshoot with the Indicators
Recommended Action
Apply power.
None.
Verify module installation, no modules removed,
and correct, as needed.
Check network cabling, and correct, as needed.
Recommended Action
1. Verify field power is on.
2. Verify backplane power (load current) is not exceeded.
3. Replace 1734-APB adapter.
None.
Apply field power (24V).
None.
Publication 1734-UM001D-EN-P - April 2008
161