2. From the Configuration dialog, complete the entries, referring to the
table for information about how to complete entries with No Load
Detection.
Feature
Description
Point
Displays the channel numbers.
• Use to determine how a status bit acts after the cause of the
Latch Faults
fault is removed.
• Use latching for tracking transient or momentary faults.
• You do not affect status LEDs when using latched alarms.
If You Select
Latch Faults
(checked)
Reset Latch Faults
(unchecked)
• The Reset mode defines the action of the output during a
Auto Restart
short circuit or overload.
• A fault also occurs if you turn on an output when you do not
apply field power to it.
Select
Latched off (unchecked)
Auto restart (checked)
• Select to clear latched alarms.
Point Fault
• A blue arrow denotes the use of explicit messaging.
3. At the top of the Configuration dialog, complete the header check boxes
for the following:
• No Load Detection
• Latch Faults
• Auto Restart
Configure POINT I/O Modules in RSLogix 5000 Software
Then
Alarm bits stay faulted if an alarm
occurs. Clear the fault by using the
clear latched alarm service for the
channel (Reset pushbutton).
Alarm bits reflect the present state.
If you want the output to
Shut off
Continually try to turn on
Publication 1734-UM001D-EN-P - April 2008