Features Specific To All Flex 5000 Output Modules; Output State Change Time; Configurable Point-Level Output State In Program Mode Or; Communications Fault Mode - Rockwell Automation 5094-IA16 User Manual

Standard and safety i/o modules
Table of Contents

Advertisement

Chapter 4
Output Module Features
Features Specific to All
FLEX 5000 Output Modules
Standard Modules
FLEX 5000
TM
I/O
POWER
STATUS
5094-IB16
DIGITAL 16 INPUT 24 VDC
1
1 TB3
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Safety Modules
FLEX 5000
TM
I/O
POWER
STATUS
5094-IB16S
SAFETY DIGITAL 16 INPUT 24 VDC
5
5 TB3I
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
56
• 8-point standard relay output module, catalog number 5094-OW8I
• 8-point standard relay output module for extreme environments,
catalog number 5094-OW8IXT
The following topics are specific to all FLEX 5000 output modules.

Output State Change Time

Table 11
lists the time that it takes for FLEX 5000 output module outputs to
change state after a command.
Table 11 - Time for a Module Output to Change States
Module
5094-OA16, 5094-OA16XT
5094-OB8, 5094-OB8XT
5094-OB16, 5094-OB16XT
5094-OB16S, 5094-OB16SXT
5094-OB32, 5094-OB32XT
5094-OW8I, 5094-OW8IXT
5094-OW4IS, 5094-OW4ISXT
(1) The times that are listed in
Table 11
(2) Under no fault condition.

Configurable Point-level Output State in Program Mode or

Communications Fault Mode

You can configure individual output points to specific states when the module is
in Program mode or Communications Fault mode. The following output states
are available:
• Off
• On (This option is not available for Safety applications.)
• Hold last state
To see where to configure the output states in Program mode or
Communications Fault mode, see the following:
• 5094-OA16 and 5094-OA16XT modules -
• 5094-OB8 and 5094-OB8XT modules -
• 5094-OB16 and 5094-OB16XT modules -
• 5094-OB16S and 5094-OB16SXT modules -
• 5094-OB32 and 5094-OB32XT modules -
Rockwell Automation Publication 5094-UM001E-EN-P - April 2020
(1)
Time
1/2 AC cycle (Typical)
100 μs
100 μs
4.5 ms
100 μs
10 ms
20 ms (Off to On)
10 ms (On to Off)
are from the time the module receives the message.
page 104
(2)
page 103
page 104
page 117
page 104

Advertisement

Table of Contents
loading

Table of Contents