Features Specific to All
FLEX 5000 Output Modules
Standard Modules
FLEX 5000
TM
I/O
POWER
STATUS
5094-IB16
DIGITAL 16 INPUT 24 VDC
1
1 TB3
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Safety Modules
FLEX 5000
TM
I/O
POWER
STATUS
5094-IB16S
SAFETY DIGITAL 16 INPUT 24 VDC
5
5 TB3I
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Output Module Features
Topic

Features Specific to All FLEX 5000 Output Modules

Features Specific to Only 5094-OB16 and 5094-OB16XT Modules
Feature Specific to Only 5094-OW8I and 5094-OW8IXT Modules
This chapter describes features common to these FLEX 5000™ standard and
safety output modules:
• 16-point standard DC output module, catalog number 5094-OB16
• 16-point standard DC output module for extreme environments,
catalog number 5094-OB16XT
• 16-point safety DC output module, catalog number 5094-OB16S
• 16-point safety DC output module for extreme environments,
catalog number 5094-OB16SXT
• Standard relay output module, catalog number 5094-OW8I
• Standard relay output module for extreme environments,
catalog number 5094-OW8IXT
The following topics are specific to all FLEX 5000 output modules.

Output State Change Time

Table 10
lists the time that it takes for FLEX 5000 output module outputs to
change state after a command.
Table 10 - Time for a Module Output to Change States
Module
5094-OB16, 5094-OB16XT
5094-OB16S, 5094-OB16SXT
5094-OW8I, 5094-OW8IXT
(1) The times that are listed in
Table 10
Rockwell Automation Publication 5094-UM001C-EN-P - April 2019
(1)
Time
100 μs
4.5 ms
10 ms
are from the time the module receives the message.