Rockwell Automation POINTBlock Series User Manual page 51

I/o digital and analog modules
Table of Contents

Advertisement

Do not attempt to increase load current or wattage capability
ATTENTION
beyond the maximum rating by connecting two or more
outputs in parallel. The slightest variation in relay switching
time may cause one relay to momentarily switch the total
load current.
Make certain that all relay wiring is properly connected
before applying any power to the module.
Total current draw through the wiring base unit is limited to
10 A. Separate power connections to the terminal base unit
may be necessary.
Use the end cap from your adapter or interface module to
cover the exposed interconnections on the last mounting base
on the DIN rail. Failure to do so could result in equipment
damage or injury from electric shock.
Wire with ac Modules Only using a 1734-PDN Module or
1734-PDN Module to Create a New ac Power Bus
PDN IB2
PDN
OX2
OX2
V
C
24V dc
120V ac
Wiring With ac
Modules Only
IV2
IB4
IV4 FPD OX2 OX2 OX2
120V ac or 240V ac Based on I/O Modules
Wiring Using a 1734-FPD Module To Create a New ac
Power Bus
Publication 1734-UM001D-EN-P - April 2008
Install POINT I/O Modules
51
ac Power
Bus
42090OX

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents