Calibrate the Analog
Current Output Module
To calibrate your output module, connect the module in a DeviceNet system
similar to that shown in the figure, and use this procedure.
Apply power to the power supply and module for at least 10
IMPORTANT
minutes before calibrating the module. This allows internal
temperatures to stabilize and reduces drift errors.
.
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5
250 Ω
1. Double-click the icon to bring up the General parameter dialog.
Calibrate Your Analog Modules
PDN OE2C
DeviceNet Input
0 1
0 1
Power Supply Voltage
Current Meter
Publication 1734-UM001D-EN-P - April 2008
127
0 1
0 1
0 1
0 1
44032