MORLEY-IAS

16.2 Overriding Delays on Individual Outputs

The panel allows delays to be set on individual outputs, as required.
It is recommended that a facility is provided, in the installation, to override any delayed circuits at
access Level 1.
This can be achieved in either of two ways as follows:
1.
Assign a manual call point to a zone in which all outputs act immediately.
2.
Allocate all delayed outputs to a system event. Arrange a manual call-point to generate this event.
If a specific manual call-point (pull station) is to be used for this purpose, it may be desirable to locate
the call point either adjacent to the control panel or on a main exit route and label it accordingly.

16.3 Optional Features (Operational Features With Requirements)

The Fire Alarm Control Panel has a number of optional features. The definition and
EN54
operating characteristics of these features are described below.

16.3.1 Output to fire alarm devices:

It is possible to silence the fire alarm devices at access level 2
Following silencing, it is possible to re-sound the fire alarm devices at access level 2.

16.3.2 Delays to Outputs:

The operation of delays to fire alarm devices is selected at User Level 3 and applies to:
1.
Fire detectors
2.
Manual call points
3.
Signals from specific zones.
The delay times are configurable at User Level 3 and can be adjusted in 10-second increments up to
a maximum delay of 30 minutes.
EN54-2 7.11c
Delays to
EN54
Outputs.
!
It is possible to override these delays.
The delay to one output signal does not affect the action of the other outputs.

16.3.3 Coincidence Detection:

The fire alarm control panel can inhibit the output to fire alarm devices until two or more signals are
received from detection points operating within the same zone.
When programmed to operate in this manner the following applies:
1.
It can only be selected at User Level 3.
Inhibiting the programmed fire alarm output signal in this manner does not affect the action of any
other outputs.
Page 56
Setting a delay of more than 10 minutes is non-compliant.
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
Commissioning Manual