ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
CAUTION:
This product is not compliant
EN
EN
12094-1
12094-1
with EN 12094-1.
!
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
1
EN54-2 : 8.2.4 g)
If a fault-routing output is
configured, a fault-routing
output transmission circuit
fault indication must be
provided.
or
2
8
997-457-000-8, Issue 8
January 2010

5.7.1 Output Type

Twelve (12) CBE Output Rule types are available. This
menu allows the type to be selected. The current
attributes of the selected Rule are displayed and can be
edited. To change the Rule type, from the CBE Output
Rules menu proceed as follows:
1 Press the '
the Type option from the menu. The LCD displays
the Type menu:
CBE Rule:01
4:Silence
CBE Rule:01
9:Zones
2 Using the '
Output Rule types until the required type is displayed
on the upper line, i.e. FIRE, INPUTS, FAULT, PRE-
ALARM, PLANT, FTR (Fire Transmission Relay),
RESET, DAY MODE, EXT SYSTEM, DISABLE,
THERMAL, ES SYSFLT (ES System Fault).
Note: If a fault-routing output is configured, a fault-
CBE Rule:01
: Change Rule Type
5
3 Press the '
displays only the appropriate editable settings for the
selected rule, for example:
CBE 01[FIRE
1 : Change
To change any of the settings on the CBE Output Rules
refer to Sections 5.7.2 Filter-by-type, 5.7.3
Evacuation, 5.7.4 Silence, 5.7.5 Interrupt Delay, 5.7.6
Class Change, 5.7.7 Two Zone, 5.7.8 Zones, 5.7.9
Device Inputs and 5.7.10 Soak Timer.
82
' button on the numeric keypad to select
1
1:Type
2:Filter
5:Interrupt
6:Class Change
/
' buttons, step through the CBE
2
8
routing output indication must be configured - refer
to Section 5.5.1.5 LED 2C Mode.
Current Type = [FIRE
: Accept < : Cancel
' button to confirm selection. The LCD
5
][ANY] 1 - - - - - - - - - - - - - - - - - - - - 1 6
[EvSlln
] YYYYNNYYNDDNCCNN
3:Evac
: More
7:Two Zone
: More
]

Advertisement