Master Programming Level
ZONE SETUP
1=ZONE TYPES
Zone Setup Screen #3
ZONE TYPE PROG
1=MONITOR
2=SMOKE PHOTO
3=WATERFLOW
Zone Type Program Screen #1
ZONE TYPE PROG
1=HEAT
2=PULL STATION
3=DUCT
Zone Type Program Screen #2
MS-9600 PN 51335:E1 2/14/08

3.6.3.7 Zone Type

Zone Types must be programmed only if a DACT, programmed for zone reporting,
is installed on the control panel. Pressing 1 for Zone Types, while viewing Zone
Setup Screen #3, will display a screen similar to the following:
ZONE TYPE PROG
1=Z00
2=Z01
3=Z02
Zones Installed Screen
This display will show the system zones (default and user programmed) and their
associated types. Note that an up and/or down arrow will appear in the upper right
corner of the display, indicating that additional screens of zone information exists.
Press the up or down arrow keys to view zones Z00 through Z99.
Zone types can be changed by pressing the keypad number key corresponding to the
zone in each Zones Installed Screen. Available zone types will be displayed in the
resultant screens. For example, to change the zone type for zone Z02 in the screen
illustrated above, press 3. The following screens will be displayed:
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type
Program Screen #2 is displayed. Press 2 to program zone Z02 as a Pull Station
zone. The display will return to the Zones Installed Screen showing zone Z02 and
the Pull Station program type. Repeat the procedure for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will
assign a Waterflow silenceable zone type to the selected zone. Any signaling
devices programmed to the same zone can be silenced by pressing the Alarm Silence
key or by using the auto-silence feature.
To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page
81.
MONITOR
MONITOR
MONITOR
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
3=TAMPER
Zone Type Program Screen #3
ZONE TYPE PROG
1=SUPERVISORY
2=PROC. MON
3=SMOKE ION
Zone Type Program Screen #4
Programming
79