SubCode
52
During the control phase, the system sends a HeartBeat message to the slave every 100 ms and checks the
Op state via HeartBeat producer message sent by the device, which must arrive within the time set in object
1017. If an error occurs it returns to Init .
If HeartBeat is not available and NodeGuarding is active instead, the timeout values set in objects 100C and
100D are used.
Among the objects requested during the configuration phase are those which contain the mapping, the mean-
ing of the data in the PDOs. The objects the slave may have mapped in the PDOs are a subset of those de-
fined by the DS401 profile. In particular, the list indicates objects recognised by the drive:
6000h Read Input 8 bit
6100h ReadInput 16 bit
6120h ReadInput 32 bit
6200h Write Output 8 bit
6300h WriteOutput 16 bit
6320h WriteOutput 32 bit
6400h ReadAnalog 8 bit
6401h ReadAnalog 16 bit
6411h WriteAnalog 16 bit
The configuration does not fail if other objects are detected, however the object in the PDO is not managed
when received and is written as 0 for transmission.
The objects are associated with the analog and digital input and output parameters in the order they are de-
tected.
For example, if the slave is configured as follows
1600
1
2
1601
1
2
The data sent via RPDO will be associated in this order
Byte 0
|
V
Byte 0
6200h
Byte 0
|
|
V
Byte 0
6200h
Following the transition to Op, the drive software reads and writes the PDOs (RPDO) and moves the data to
the I/O control blocks and periodically sends the Sync message.
Since there are only 2 devices in the network and data exchange is predefined, synchronous PDOs are always
used to have repeatability in communication.
Data are exchanged in communciation cycles, the duration of which is predefined with parameter 5488 "Ex-
ternal IO period" (available in the service menu and via the .sco configuration file). The default communication
cycle value is 8 ms.
282
Index
0x1803
6200h
6200h
6300h
6300h
Byte1
Byte2
|
V
Byte1
Byte2
6200h
--
Byte1
Digital out 0Ext mon
|
Byte 0
|
|
V
V
Byte1
Byte2
6200h
--
SubIndex
1
Byte3
Digital out 0Ext mon
Byte3
PDO1
--
Byte1
|
V
Byte3
--
Notes
TPDO4 enable
Digital out 1Ext mon
PDO1
ADV200 • Appendix