gefran ADV200 Functions Description And Parameters List page 163

Field oriented vector ac drive for asyncronous motors
Hide thumbs Also See for ADV200:
Table of Contents

Advertisement

Menu
PAR
Description
24.33
4604 InAir restart time
Setting of the time within which the Intakeair OT [11] alarm must be reset in order to perform automatic re-
start.
Menu
PAR
Description
24.34
4606 InAir holdoff
Setting of the delay between the signalling of the intake air overtemperature alarm Intakeair OT [11] and ena-
bling of the alarm. If an alarm condition occurs, the drive will wait for the set time before enabling the alarm. If
the alarm is removed within the set time, the drive will not indicate any alarm condition.
Menu
PAR
Description
24.35
4610 Desat restart
Enabling of automatic restart after the desaturation alarm Desat. This alarm indicates a short circuit between
the motor phases or on the power bridge.
0 Disable
1 Enable
Menu
PAR
Description
24.36
4612 Desat restart time
Setting of the time within which the Desaturation alarm must be reset in order to perform automatic restart.
(Time with alarm signal active + 1000 msec).
Menu
PAR
Description
24.37
4620 IOverC restart
Enabling of automatic restart after the drive overcurrent alarm. This alarm indicates an overcurrent (or short
circuit between phases or towards the ground).
0 Disable
1 Enable
Menu
PAR
Description
24.38
4622 IOverC restart time
Setting of the time within which the Overcurrent alarm must be reset in order to perform automatic restart.
(Time with alarm signal active + 1000 msec).
Menu
PAR
Description
24.39
4630 OverV restart
Enabling of automatic restart after the overvoltage alarm. This alarm indicates an overvoltage on the intermedi-
ate circuit (DC link)
0 Disable
1 Enable
Menu
PAR
Description
24.40
4632 OverV restart time
Setting of the time within which the Overvoltage alarm must be reset in order to perform automatic restart.
(Time with alarm signal active + 1000 msec).
Menu
PAR
Description
24.41
4640 UnderV restart
Enabling of automatic restart after the undervoltage alarm. This alarm indicates an undervoltage on the inter-
ADV200 • Functions description and parameters list
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ENUM
Def
Min
1000
120
Def
Min
10000
0
Def
Min
Disable
0
Def
Min
2000
1000
Def
Min
Disable
0
Def
Min
2000
1000
Def
Min
Disable
0
Def
Min
2000
1000
Def
Min
Enable
0
Max
Acc
Mod
30000
ERW FVS
Max
Acc
Mod
30000
ERW FVS
Max
Acc
Mod
1
ERW FVS
Max
Acc
Mod
10000
ERW FVS
Max
Acc
Mod
1
ERW FVS
Max
Acc
Mod
10000
ERW FVS
Max
Acc
Mod
1
ERW FVS
Max
Acc
Mod
10000
ERW FVS
Max
Acc
Mod
1
ERW FVS
163