gefran ADV200 Functions Description And Parameters List page 180

Field oriented vector ac drive for asyncronous motors
Hide thumbs Also See for ADV200:
Table of Contents

Advertisement

Code
Error message shown on
the display
12
Motor OT
13
Drive overload
14
Motor overload
15
Bres overload
16
Phaseloss
17
Opt Bus fault
18
Opt 1 IO fault
19
Opt 2 IO fault
20
Opt Enc fault
21
External fault
22
Speed fbk loss
180
Sub-code
Condition: Motor overtemperature alarm. Possible causes:
- Load cycle too heavy
- The motor is installed in a place where the ambient temperature is too high
- If the motor is provided with a blower: the fan is not working
- If the motor is not provided with a blower: the load is too high at slow speeds. Cooling the fan on the mo-
tor shaft is not sufficient for this load cycle.
- The motor is used at less than the rated frequency, causing additional magnetic losses.
Solution:
- Change the processing cycle.
- Use a cooling fan to cool the motor.
Condition: Drive overload alarm.
The overload threshold of the accumulator of the I²t drive thermal image has been exceeded.
Solution: Check that the size of the drive is suitable for the application.
Condition: Motor overload alarm.
The current absorbed during operation is greater than that specified on the motor data plate. The overload
threshold of the accumulator of the I²t motor thermal image has been exceeded.
Solution:
- Reduce the motor load.
- Increase the size of the motor.
Condition: Braking resistor overload alarm.
The current absorbed by the resistor is greater than the rated current. The overload threshold of the ac-
cumulator of the I²t braking resistor thermal image has been exceeded.
Solution: Increase the Watt value of the braking resistor
Condition: Power phase loss alarm.
Solution: Check the mains voltage and whether any protections upstream of the drive have been tripped.
Condition: Error in the configuration stage or communication error.
XXX0H-X
If the first digit to the left of "H" in the alarm sub-code is 0, the error regards a communica-
tion problem.
XXXXH-X
If the first digit to the left of "H" in the alarm sub-code is other than 0, the error regards a
configuration problem.
Solution: For configuration errors, check the configuration of the bus communication, type of bus,
baudrate, address, parameter setting.
For communication errors verify wiring, resistance of terminations, interference immunity, timeout settings.
For further details, please refer to the user guide for the specific bus.
Condition: Error in the communication between Regulation and I/O expansion card in slot 1
Solution: Check that it has been inserted correctly, see chapter 10.5 ADV200 QS manual.
Condition: Error in the communication between Regulation and I/O expansion card in slot 2 or 3
Solution: Check that it has been inserted correctly, see chapter 10.5 ADV200 QS manual.
Condition: Error in the communication between Regulation and Encoder feedback card.
Solution: Check that it has been inserted correctly, see chapter 10.5 ADV200 QS manual.
Condition: External alarm present.
A digital input has been programmed as an external alarm, but the +24V voltage is not available on the
terminal.
Solution: Check that the terminal screws are tight
Condition: Speed feedback loss alarm.
The encoder is not connected, not connected properly or not powered: verify encoder operation by select-
ing the Motor speed parameter in the MONITOR menu.
Description
ADV200 • Troubleshooting