0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu
PAR
Description
24.27
4572 Motor ovld activity
Setting of the behaviour of the drive in case of a motor overload alarm Motor ovld [14]. This alarm indicates
that the motor overload threshold has been reached.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu
PAR
Description
24.28
4574 Bres ovld activity
Setting of the behaviour of the drive in case of a braking resistor overload alarm Bres ovld. This alarm indi-
cates that the braking resistor overload threshold has been reached.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu
PAR
Description
24.29
4582 HTsens restart
Enabling of automatic restart after the drive heatsink overtemperature alarm HeatsinkS OTUT [10].
0 Disable
1 Enable
Menu
PAR
Description
24.30
4584 HTsens restart time
Setting of the time within which the HeatsinkS OTUT [10] alarm must be reset in order to perform automatic
restart.
Menu
PAR
Description
24.31
4600 InAir activity
Setting of the behaviour of the drive in case of an intake air overtemperature alarm Intakeair OT [11].This
alarm indicates that the temperature of the intake cooling air is too high.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu
PAR
Description
24.32
4602 InAir restart
Enabling of automatic restart after the intake air overtemperature alarm Intakeair OT [11].
0 Disable
1 Enable
162
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
Def
Min
Warning
0
Def
Min
Disable
0
Def
Min
Disable
0
Def
Min
20000
120
Def
Min
Stop
0
Def
Min
Disable
0
ADV200 • Functions description and parameters list
Max
Acc
Mod
4
ERW FVS
Max
Acc
Mod
4
ERW FVS
Max
Acc
Mod
1
ERW FVS
Max
Acc
Mod
60000
ERW FVS
Max
Acc
Mod
4
ERW FVS
Max
Acc
Mod
1
ERW FVS