gefran ADV200 Functions Description And Parameters List page 122

Field oriented vector ac drive for asyncronous motors
Hide thumbs Also See for ADV200:
Table of Contents

Advertisement

If set to 1 the Powerloss function is enabled. In case of a power failure the function is enabled to try to control
the motor speed and prevent the intervention of the Undervoltage alarm.
Menu
PAR
Description
22.9.2 3402 Powerloss accel time
Setting of the acceleration time used in the Powerloss operating mode. The acceleration ramp time is used
when Powerloss mode = Restart has been selected and must be adjusted to suit machine requirements.
Menu
PAR
Description
22.9.3 3404 Powerloss decel time
Setting of the deceleration time used during Powerloss operating mode.
The deceleration ramp time must be short enough (in case of low speeds) to allow the drive to enter regenera-
tion mode quickly, otherwise the Undervoltage alarm is generated. If the deceleration ramp time setting is
too short, when the drive enters regeneration mode it might not be able to control the DC link voltage and the
Overvoltage alarm would be generated.
Longer deceleration times are necessary at high motor speeds to prevent the Overvoltage alarm from being
generated.
This parameter must be adjusted so as to reach a compromise between low speed and high speed motor
operation.
Menu
PAR
Description
22.9.4 3410 Powerloss Vdcref
Setting of the voltage control limit on the DC-link during a controlled stop with loss of supply voltage The maxi-
mum value that can be set is the drive overvoltage limit.
Menu
PAR
Description
22.9.5 3420 Powerloss P gain
Setting of the proportional gain during the Powerloss function.
Increase in case of Overvoltage error; the Undervoltage alarm can also be prevented by increasing the decel-
eration time.
Increase if the DC link voltage is set to a value other than the setpoint.
Menu
PAR
Description
22.9.6 3422 Powerloss I gain
Setting of the integral gain during the Powerloss function.
Reduce if the DC link voltage is set to a value other than the setpoint.
Menu
PAR
Description
22.9.7 3438 Powerloss mode
This parameter is used to configure the behaviour of the Powerloss function when the mains supply is restored.
It is possible to set whether the drive should continue at zero speed or return to the setpoint when the mains
supply is restored. The drive does not automatically recognise the fact that the mains supply has been re-
stored. This information must be supplied from the outside via the Powerloss mains src digital input.
0 Ramp down
1 Restart
122
UM
Type
FB BIT
s
FLOAT
UM
Type
FB BIT
s
FLOAT
UM
Type
FB BIT
V
FLOAT
UM
Type
FB BIT
A/V
FLOAT
UM
Type
FB BIT
ms
FLOAT
UM
Type
FB BIT
ENUM
Def
Min
10.0
0.01
Def
Min
2.0
0.01
Def
Min
CALCF
0.0
Def
Min
CALCF
0
Def
Min
CALCF
1.0
Def
Min
Ramp down
0
ADV200 • Functions description and parameters list
Max
Acc
Mod
100.0
ERW F__
Max
Acc
Mod
100.0
ERW F__
Max
Acc
Mod
CALCF
ERWZS FV_
Max
Acc
Mod
100.000
ERWS F__
Max
Acc
Mod
1000.0
ERWS F__
Max
Acc
Mod
1
ERWZ F__

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents