Grouped Elements; Overview; Setting Group; Line Differential Elements - GE L30 Instruction Manual

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5 SETTINGS

5.6GROUPED ELEMENTS

Each protection element can be assigned up to six different sets of settings according to setting group designations 1 to 6.
The performance of these elements is defined by the active setting group at a given time. Multiple setting groups allow the
user to conveniently change protection settings for different operating situations (for example, altered power system config-
uration, season of the year, etc.). The active setting group can be preset or selected via the
Control elements section later in this chapter). See also the Introduction to elements section at the beginning of this chap-
ter.

PATH: SETTINGS
GROUPED ELEMENTS
 SETTING GROUP 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if
no other group is active (see the Control elements section for additional details).
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
 LINE DIFFERENTIAL
 ELEMENTS
MESSAGE
GE Multilin

SETTING GROUP 1(6)

 LINE DIFFERENTIAL
 ELEMENTS
 PHASE CURRENT
 NEUTRAL CURRENT
 GROUND CURRENT
 NEGATIVE SEQUENCE
 CURRENT
 BREAKER FAILURE
 VOLTAGE ELEMENTS
 SUPERVISING
 ELEMENTS
SETTING GROUP 1(6)

LINE DIFFERENTIAL ELEMENTS

 CURRENT
 DIFFERENTIAL
 STUB BUS
L30 Line Current Differential System
5.6 GROUPED ELEMENTS

5.6.1 OVERVIEW

SETTING GROUPS
5.6.2 SETTING GROUP
See page 5-123.
See page 5-129.
See page 5-140.
See page 5-147.
See page 5-150.
See page 5-152.
See page 5-161.
See page 5-168.
5.6.3 LINE DIFFERENTIAL ELEMENTS
See page 5-124.
See page 5-128.