5.2.

CONTROL SETTINGS FOR INPUTS/OUTPUTS

This section explains the settings related to CIO inputs/outputs. Modification of these values is performed using the
master unit communication software, EnerVista F650Setup for F650, or GE-CONF for F600.
Settings relative to I/O boards are described in table 5-1:
SETTING
I/O board type (available only for
CIO modules)
Input activation voltage threshold
Group A
Input activation voltage threshold
Group B
Debounce time Group A
Debounce time Group B
Input type
Input signal time delay
Output logic type
Output type
Output pulse length
Being:
X
I/O board name, depending on the CIO model.
For the I/O board selection in the relay model, associated digits to each board type are as follows:
ASSOCIATED DIGIT
32
I/O MODULES DESCRIPTION
TABLE 5-1 I/O BOARD SETTINGS
HMI
I/O Board_X Type
Voltage Threshold A_X
Voltage Threshold B_X
Debounce Time A_X
Debounce Time B_X
Input Type_X_CCY
Delay Input
Time_X_CCY
Output Logic_X_0Z
Output Type_X_0Z
Pulse Output
Time_X_0Z
F650PC BOARD
0
1
16 INP+ 8OUT
2
8 INP +8 OUT +SUPV
CIO Remote CAN Digital I/O Module
5.2.1.
DEFAULT
NONE
80
80
15
15
POSITIVE
0
POSITIVE
NORMAL
0
SETTINGS
NONE

INPUT/OUTPUT BOARDS SETTINGS

RANGE
16 INP + 8OUT
8 INP + 8OUT +
SUPV
NONE
0 – 255 V
0 – 255 V
1 – 50 ms
1 – 50 ms
POSITIVE-EDGE
NEGATIVE-EDGE
POSITIVE
NEGATIVE
0 – 60000 ms
POSITIVE-
NEGATIVE
NORMAL
PULSE
LATCH
0 – 60000 ms
BOARD TYPE
None
Mixed
Supervision
GEK-106465A
STEP
N/A
1 V
1 V
1 ms
1 ms
N/A
1 ms
N/A
N/A
1 ms

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multilin cioh1j1hi

Table of Contents