Power Swing Detect - GE UR Series Instruction Manual

Line differential relay
Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
ÖØ
PATH: SETTINGS
GROUPED ELEMENTS
POWER SWING
DETECT
5
5-72
Ö
SETTING GROUP 1(8)
POWER SWING
FUNCTION: Disabled
POWER SWING
MESSAGE
SOURCE: SRC 1
POWER SWING
MESSAGE
MODE: Two Step
POWER SWING
MESSAGE
SUPV: 0.600 pu
POWER SWING FWD
MESSAGE
REACH: 50.00 ohms
POWER SWING FWD
MESSAGE
RCA: 75°
POWER SWING REV
MESSAGE
REACH: 50.00 ohms
POWER SWING REV
MESSAGE
RCA: 75°
POWER SWING OUTER
MESSAGE
LIMIT ANGLE: 120°
POWER SWING MIDDLE
MESSAGE
LIMIT ANGLE: 90°
POWER SWING INNER
MESSAGE
LIMIT ANGLE: 60°
POWER SWING PICKUP
MESSAGE
DELAY 1: 0.030 s
POWER SWING RESET
MESSAGE
DELAY 1: 0.050 s
POWER SWING PICKUP
MESSAGE
DELAY 2: 0.017 s
POWER SWING PICKUP
MESSAGE
DELAY 3: 0.009 s
POWER SWING PICKUP
MESSAGE
DELAY 4: 0.017 s
POWER SWING SEAL-IN
MESSAGE
DELAY 1: 0.400 s
POWER SWING TRIP
MESSAGE
MODE: Delayed
POWER SWING BLK:
MESSAGE
Off
POWER SWING
MESSAGE
TARGET: Self-Reset
POWER SWING
MESSAGE
EVENTS: Disabled
L90 Line Differential Relay

5.5.8 POWER SWING DETECT

ÖØ
POWER SWING DETECT
Range: Disabled, Enabled
Range: SRC 1,..., SRC 6
Range: Two Step, Three Step
Range: 0.050 to 30.000 pu in steps of 0.001
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 40 to 90° in steps of 1
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 40 to 90° in steps of 1
Range: 40 to 140° in steps of 1
Range: 40 to 140° in steps of 1
Range: 40 to 140° in steps of 1
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Early, Delayed
Range: Flexlogic™ operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS