GE UR Series Instruction Manual page 99

Line differential relay
Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

5 SETTINGS
Ö
PATH: SETTINGS
PRODUCT SETUP
MODBUS USER MAP
MESSAGE
®
The Modbus
User Map provides up to 256 registers with read only access. To obtain a value for a memory map address,
enter the desired location in the
ing value from the is displayed in the
values for the previous
ADDRESS
values of "0" will be displayed for all registers.
Different
values can be entered as required in any of the register positions.
ADDRESS
These settings can also be used with the DNP protocol. See the DNP ANALOG INPUT POINTS section in
Appendix E for details.
NOTE
Ö
PATH: SETTINGS
PRODUCT SETUP
REAL TIME
CLOCK
The date and time for the relay clock can be synchronized to other relays using an IRIG-B signal. It has the same accuracy
as an electronic watch, approximately ±1 minute per month.
An IRIG-B signal may be connected to the relay to synchronize the clock to a known time base and to other relays. If an
IRIG-B signal is used, only the current year needs to be entered.
Ø
See also the
COMMANDS
SET DATE AND TIME
Ö
PATH: SETTINGS
PRODUCT SETUP
FAULT REPORT
MESSAGE
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data will include:
Name of the relay, programmed by the user
Date and time of trigger
Name of trigger (specific operand)
Active setting group
Pre-fault current and voltage phasors (one-quarter cycle before the trigger)
Fault current and voltage phasors (three-quarter cycle after the trigger)
Target Messages that are set at the time of triggering
Events (9 before trigger and 7 after trigger)
The captured data also includes the fault type and the distance to the fault location, as well as the reclose shot number.
GE Power Management
ÖØ
MODBUS USER MAP
ADDRESS
1:
VALUE:
0
ADDRESS 256:
VALUE:
0
line (the value must be converted from hex to decimal format). The correspond-
ADDRESS
line. A value of "0" in subsequent register
VALUE
lines incremented by "1". An address value of "0" in the initial register means "none" and
ÖØ
REAL TIME CLOCK
IRIG-B SIGNAL TYPE:
None
menu for manually setting the relay clock.
ÖØ
FAULT REPORT
FAULT REPORT
SOURCE: SRC 1
FAULT REPORT TRIG:
Off
L90 Line Differential Relay
5.2.4 MODBUS
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
ADDRESS
Range: None, DC Shift, Amplitude Modulated
Range: SRC 1, SRC 2,..., SRC 6
Range: FlexLogic™ operand
5.2 PRODUCT SETUP
®
USER MAP
lines automatically return
5.2.5 REAL TIME CLOCK
5.2.6 FAULT REPORT