Download  Print this page

GE UR Series Instruction Manual Page 180

Line differential relay.
Hide thumbs
   
1
2
3
4
Table of Contents
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470

Advertisement

5.5 GROUPED ELEMENTS
Figure 5–44: NEUTRAL DIRECTIONAL VOLTAGE-POLARIZED CHARACTERISTICS
5
The above figure shows the voltage-polarized phase angle comparator characteristics for a phase-A to ground fault, with:
ECA
= 90° (Element Characteristic Angle = centerline of operating characteristic)
FWD LA
= 80° (Forward Limit Angle = the ± angular limit with the ECA for operation)
REV LA
= 80° (Reverse Limit Angle = the ± angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is designed to emu-
late an electromechanical directional device. Larger operating and polarizing signals will result in faster directional discrimi-
nation bringing more security to the element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and therefore,
should be used for the tripping direction. The reverse-looking function is designed to be faster as compared to the forward-
looking function and should be used for the blocking direction. This allows for better protection coordination.
The above bias should be taken into account when using the Neutral Directional Overcurrent element to 'directionalize'
other protection elements.
NEUTRAL DIR OC1 POLARIZING:
This setting selects the polarizing mode for the directional unit.
If "Voltage" polarizing is selected, the element uses the zero-sequence voltage angle for polarization. The user can use
either the zero-sequence voltage V_0 calculated from the phase voltages, or the zero-sequence voltage supplied
externally as the auxiliary voltage Vx, both from the
The calculated V_0 can be used as polarizing voltage only if the voltage transformers are connected in Wye. The aux-
iliary voltage can be used as the polarizing voltage provided
ILIARY VT CONNECTION
open delta connected secondary of VTs).
The zero-sequence voltage (V_0) or auxiliary voltage (Vx), accordingly, must be higher than 1 V secondary to be vali-
dated for use as a polarizing signal. If the polarizing signal is not valid, neither forward nor reverse indication is given.
If "Current" polarizing is selected, the element uses the ground current angle connected externally and configured
under
NEUTRAL OC1 SOURCE
and neutral point of an adequate local source of ground current. The ground current must be higher than 0.05 pu to be
5-96
REV LA
–3V_0 line
line
REV Operating
Region
LA
–ECA line
–3I_0 line
VCG
LA
REV LA
line
is set to "Vn" and the auxiliary voltage is connected to a zero-sequence voltage source (such as
for polarization. The ground current transformer must be connected between the ground
L90 Line Differential Relay
FWD LA
line
VAG
(reference)
FWD Operating
LA
ECA
LA
VBG
FWD LA
line
3V_0 line
.
NEUTRAL DIR OC1 SOURCE
Ö
SYSTEM SETUP
AC INPUTS
5 SETTINGS
Region
3I_0 line
ECA line
827805A1.CDR
ÖØ
ÖØ
VOLTAGE BANK
GE Power Management
AUX-

Advertisement

Table of Contents

   Also See for GE UR Series

   Related Manuals for GE UR Series

This manual is also suitable for:

L90

Comments to this Manuals

Symbols: 0
Latest comments: