GE UR Series Instruction Manual page 390

Line differential relay
Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 26 of 38)
ADDR
REGISTER NAME
9A1B
...Repeated for module number 14
9A1D
...Repeated for module number 15
9A1F
...Repeated for module number 16
Setting Groups (Read/Write Setting)
A000
Setting Group for Modbus Comm (0 means group 1)
B
A001
Setting Groups Block
A002
FlexLogic Operands to Activate Grps 2 to 8 (7 items)
A009
Setting Group Function
A00A
Setting Group Events
Setting Groups (Read Only)
A00B
Current Setting Group
VT Fuse Failure (Read/Write Setting) (6 modules)
A040
VT Fuse Failure Function
A041
...Repeated for module number 2
A042
...Repeated for module number 3
A043
...Repeated for module number 4
A044
...Repeated for module number 5
A045
...Repeated for module number 6
Pilot POTT (Read/Write Setting)
A070
POTT Scheme Function
A071
POTT Permissive Echo
A072
POTT Rx Pickup Delay
A073
POTT Transient Block Pickup Delay
A074
POTT Transient Block Reset Delay
A075
POTT Echo Duration
A076
POTT Line End Open Pickup Delay
A077
POTT Seal In Delay
A078
POTT Ground Direction OC Forward
A079
POTT Rx
A07A
POTT Echo Lockout
Digital Elements (Read/Write Setting) (16 modules)
B000
Digital Element x Function
B001
Digital Element x Name
B015
Digital Element x Input
B016
Digital Element x Pickup Delay
B018
Digital Element x Reset Delay
B01A
Digital Element x Block
B01B
Digital Element x Target
B01C
Digital Element x Events
B01D
Digital Element x Reserved (3 items)
B020
...Repeated for module number 2
B040
...Repeated for module number 3
B060
...Repeated for module number 4
B080
...Repeated for module number 5
B0A0
...Repeated for module number 6
B0C0
...Repeated for module number 7
B0E0
...Repeated for module number 8
B100
...Repeated for module number 9
B120
...Repeated for module number 10
B140
...Repeated for module number 11
B160
...Repeated for module number 12
B180
...Repeated for module number 13
B1A0
...Repeated for module number 14
B1C0
...Repeated for module number 15
B-34
RANGE
0 to 7
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 7
0 to 1
0 to 1
0 to 1
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65535
0 to 65535
0 to 65.535
0 to 1
---
0 to 65535
0 to 999999.999
0 to 999999.999
0 to 65535
0 to 2
0 to 1
---
L90 Line Differential Relay
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
1
F102
---
1
F102
---
1
F102
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F300
s
0.001
F001
---
1
F102
---
---
F203
---
1
F300
s
0.001
F003
s
0.001
F003
---
1
F300
---
1
F109
---
1
F102
---
---
F001
GE Power Management
DEFAULT
0
0
0
0 (Disabled)
0 (Disabled)
0
0 (Disabled)
0 (Disabled)
0 (Disabled)
0
20
90
100
50
400
0
0
250
0 (Disabled)
"Dig Element 1 "
0
0
0
0
0 (Self-reset)
0 (Disabled)
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

L90

Table of Contents