APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 13 of 38)
ADDR
REGISTER NAME
4584
Source Ground CT
4585
Source Phase VT
4586
Source Auxiliary VT
4587
...Repeated for module number 2
458E
...Repeated for module number 3
4595
...Repeated for module number 4
459C
...Repeated for module number 5
45A3
...Repeated for module number 6
Power System (Read/Write Setting)
4600
Nominal Frequency
4601
Phase Rotation
4602
Frequency And Phase Reference
4603
Frequency Tracking
L90 Power System (Read/Write Setting)
4610
L90 Number of Terminals
4611
L90 Number of Channels
4612
Charging Current Compensation
4613
Positive Sequence Reactance
4614
Zero Sequence Reactance
4615
Zero Sequence Current Removal
4616
Local Relay ID
4617
Terminal 1 ID
4618
Terminal 2 ID
Line (Read/Write Setting)
46D0
Line Pos Seq Impedance
46D1
Line Pos Seq Impedance Angle
46D2
Line Zero Seq Impedance
46D3
Line Zero Seq Impedance Angle
46D4
Line Length Units
46D5
Line Length
Breaker Control Global Settings (Read/Write Setting)
46F0
UCA XCBR x SelTimOut
Breaker Control (Read/Write Setting) (2 modules)
4700
Breaker x Function
4701
Breaker x Name
4704
Breaker x Mode
4705
Breaker x Open
4706
Breaker x Close
4707
Breaker x Phase A 3 Pole
4708
Breaker x Phase B
4709
Breaker x Phase C
470A
Breaker x External Alarm
470B
Breaker x Alarm Delay
470D
Breaker x Push Button Control
470E
Breaker x Manual Close Recal Time
4710
Breaker x UCA XCBR x SBOClass
4711
Breaker x UCA XCBR x SBOEna
4712
Breaker x Out Of Service
4713
Reserved (5 items)
4718
...Repeated for module number 2
Synchrocheck (Read/Write Setting) (2 modules)
4780
Synchrocheck Function
4781
Synchrocheck V1 Source
4782
Synchrocheck V2 Source
GE Power Management
RANGE
0 to 63
0 to 63
0 to 63
25 to 60
0 to 1
0 to 5
0 to 1
2 to 3
1 to 2
0 to 1
0.1 to 65.535
0.1 to 65.535
0 to 1
0 to 255
0 to 255
0 to 255
0.01 to 250
25 to 90
0.01 to 650
25 to 90
0 to 1
0 to 2000
1 to 60
0 to 1
---
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1000000
0 to 1
0 to 1000000
1 to 2
0 to 1
0 to 65535
0 to 65535
0 to 1
0 to 5
0 to 5
L90 Line Differential Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F400
---
1
F400
---
1
F400
Hz
1
F001
---
1
F106
---
1
F167
---
1
F102
---
1
F001
---
1
F001
---
1
F102
0.001
F001
0.001
F001
---
1
F102
---
1
F001
---
1
F001
---
1
F001
Þ
0.01
F001
°
1
F001
Þ
0.01
F001
°
1
F001
---
1
F147
---
0.1
F001
s
1
F001
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
---
1
F102
s
0.001
F003
---
1
F001
---
1
F102
---
1
F300
1
F001
---
1
F102
---
1
F167
---
1
F167
DEFAULT
0
0
0
B
60
0 (ABC)
0 (SRC 1)
1 (Enabled)
2
1
0 (Disabled)
100
100
0 (Disabled)
0
0
0
300
75
900
75
0 (km)
1000
30
0 (Disabled)
"Bkr 1 "
0 (3-Pole)
0
0
0
0
0
0
0
0 (Disabled)
0
1
0 (Disabled)
0
0
0 (Disabled)
0 (SRC 1)
1 (SRC 2)