5 SETTINGS
5.5 GROUPED ELEMENTS
Each protection element can be assigned up to 8 different sets of settings according to SETTING GROUP designations 1
to 8. The performance of these elements is defined by the active SETTING GROUP at a given time. Multiple setting groups
allow the user to conveniently change protection settings for different operating situations (e.g. altered power system con-
figuration, season of the year). The active setting group can be preset or selected via the SETTING GROUPS menu (see
the CONTROL ELEMENTS section). See also the INTRODUCTION TO ELEMENTS section at the front of this chapter.
Ø
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Each of the 8 SETTING GROUP menus is identical. SETTING GROUP 1 (the default active group) automatically becomes
active if no other group is active (see the CONTROL ELEMENTS section for additional details).
Ø
PATH: SETTINGS
GROUPED ELEMENTS
LINE DIFFERENTIAL
ELEMENTS
MESSAGE
GE Power Management
Ö
SETTING GROUP 1(8)
LINE DIFFERENTIAL
ELEMENTS
LINE PICKUP
DISTANCE
POWER SWING
DETECT
LOAD ENCROACHMENT
PHASE CURRENT
NEUTRAL CURRENT
GROUND CURRENT
NEGATIVE SEQUENCE
CURRENT
BREAKER FAILURE
VOLTAGE ELEMENTS
SUPERVISING
ELEMENTS
Ö
Ö
SETTING GROUP 1(8)
LINE DIFFERENTIAL ELEMENTS
CURRENT
DIFFERENTIAL
STUB BUS
L90 Line Differential Relay
5.5 GROUPED ELEMENTS
5.5.1 OVERVIEW
5.5.2 SETTING GROUP
See page 5-53.
See page 5-58.
See page 5-60.
See page 5-72.
See page 5-78.
See page 5-86.
See page 5-92.
See page 5-99.
See page 5-101.
See page 5-103.
See page 5-112.
See page 5-118.
5.5.3 LINE DIFFERENTIAL ELEMENTS
5
5-53