Removing The Power Supply Unit From The Left Side Of The Expansion Enclosure - IBM Storwize V7000 Unified Problem Determination Manual

Table of Contents

Advertisement

5. Using the handle, gently slide the power supply out of the enclosure, as shown
Figure 89. Removing the power supply unit from the left side of the expansion enclosure
6. Hold the new power supply so that the handle is fully extended.
7.
8. Hold the new power supply so that the handle is fully extended.
9. Connect the power cord to the power supply and to a properly grounded
Replacing a power supply unit for an expansion enclosure
You can replace either of the two 580 watt hot-swap redundant power supplies in
the expansion enclosure. These redundant power supplies operate in parallel, one
continuing to power the canister if the other fails.
in Figure 89.
Slide the power supply into the enclosure until it stops. Rotate the handle
upward into the closed position until it clicks.
electrical outlet.
Note: After the power cord is connected to the electrical outlet, make sure that
the ac and dc power (green) LEDs are lit and the fault (amber) LED is off.
Chapter 5. Control enclosure
311