Installation Planning; Appliance Height In Framing; Appliance Depth In Framing - Valor H6 Series Installation And Owner's Manual

Direct vent zero clearance gas fireplaces
Hide thumbs Also See for H6 Series:
Table of Contents

Advertisement

QUALIFIED
INSTALLER
Installer—READ THIS FIRST
Only qualifi ed licensed or trained personnel
should install this appliance.
BEFORE YOU START—YOU NEED TO KNOW
FROM THE HOMEOWNER:
• Will the optional LDK Duct Kit be used;
• The height of the unit and hearth if used;
• The thickness and type of the wall fi nish around
the fi rebox opening;
• What accessories (trim, fan, etc.) will be
installed with this fi replace;
• The venting confi guration.
1. Unpack the appliance, removing all items packed
inside and around the appliance.
2. Check that you have everything, using the Pack
Content sheet. Also, check that you have:
a fuel bed (packed separately)
a set of liners (packed separately)
Remote Battery & Wall Switch Kit RBSWK
LDK HeatShift Duct Kit (mandatory)
Gas conversion kit if necessary
Venting accessories
Electrical accessories
3. Carefully read the Installer's Checklist included
with the fi replace for the installation sequence.
38

Installation Planning

Appliance Height in Framing

Hearth considerations
• Only a non-combustible hearth can be installed in
front of the appliance if within 4" of the bottom of the
appliance.
• The top surface of the non-combustible hearth must
be at the same level as appliance bottom panel
when using certain trims and accessories—see
page 48.
• The non-combustible hearth in front of the
appliance, if within 4" of the bottom of the appliance,
must include the 1/2" Micore insulation board
provided to be used as thermal break between non-
combustible and combustible material underneath.

Appliance Depth in Framing

• 1430 Fixed Framing Kit installs at framing stage
and the appliance position is fi xed in the framing.
Wall fi nishes butt up to the frame of the 1430 Fixed
Framing Kit.
• All other trims install after the wall fi nish is applied.
The perimeter of the trims overlap the wall fi nish;
therefore the thickness of any wall fi nish materials
must be taken into consideration. The trims have
enough adjustability to allow up to 3/4" thick material
applied over top of the 1/2" thick non-combustible
board. Otherwise the appliance position within the
framing must be adjusted to allow the additional
thickness—see page 47.