Co-Linear Venting - Valor H6 Series Installation And Owner's Manual

Direct vent zero clearance gas fireplaces
Hide thumbs Also See for H6 Series:
Table of Contents

Advertisement

QUALIFIED
INSTALLER
Vertical Vent Termination
Conversion to Co-Linear Liners using Valor
1156CLA Co-Linear Adapter
Co-linear portion of vent system may only be installed
within a solid-fuel burning fi replace and chimney.
The appliance must not be connected to a chimney fl ue
serving a separate solid-fuel burning appliance.
Requires the Valor Co-Axial to Co-Linear appliance
Adapter 1156CLA, two lengths of 2-ply, one 3" and one
4" diameter fl exible chimney liner approved for venting
gas appliances, a co-linear termination kit and fl ashing
or a co-linear to co-axial adapter and either a high
wind vertical vent terminal cap or a low profi le vertical
termination.
Note: A 3" diameter exhaust liner may be used if
conditions will not allow for the 4" exhaust liner. Cold
start-up problems may be experienced however when
using a 3" exhaust liner.
Firebox zero clearance standoff s supplied with the
heater are not required for this application.
Rules for Co-Linear Venting
• Maximum 40 feet vertical pipe
• Minimum 10 feet vertical
• Maximum off set 8 feet with liners at minimum
45 degrees from horizontal plane
• Restrictor: Use #4 position for all co-linear
installations—refer to page 36 for restrictor
36
Co-axial Venting
Roof
Minimum
Pitch
"H" (feet)
Flat to 7/12
1'
Over 7/12 to
1.5'
8/12
Over 8/12 to
2'
9/12
Over 9/12 to
2.5'
10/12
Over 10/12 to
3.25'
11/12
Over 11/12 to
4'
12/12
Over 12/12 to
5'
14/12

Co-linear Venting

Horizontal
overhang
Vertical
wall
Storm
collar
Roof
flashing
3" intake
4" exhaust
liner
liner
Co-linear
adapter
3" min. bend radius
for intake liner and
4" min. bend radius
for exhaust liner
Any fi nishes
applied above
the fi replace's
opening must be
non-combustible
Co-Linear installation into existing F/P
Overhang should not
extend beyond vent if
within 48" of
termination cap
Termination
Min. 24"
cap
(unvented soffit)
Min. 36"
Min.
(vented soffit)
18"
'H'
Approved 4 x 3 co-linear
termination
Flashing
1156
Co-linear
adapter
Engine
1 x 3"
intake
liner
and
1 x 4"
exhaust
liner