8.3.3
Step 3, zone processing on alarm
8.3.4
Step 4, LED activation mode
8.3.5
Step 5, activation mode of control lines
Building Technologies
Fire Safety & Security Products
Option
Setting
Function: Zone alarm processing (zone type)
1
via timer V1/V2
2
direct (timer bypassed) 1)
3
Alarm 0 (internal) 1)
- RT and timer V1/V2 not initiated
- Horn activated (unless disengaged in step 7)
4
via timer V1/V2, but call points always initiate
Alarm 2 (direct)
see also chapter 5.1.4 manual, manual call
point detection
1)
If all zones are set to direct or internal, the function manned/unmanned is disabled.
Option
Setting
Function: Activation of LED remote transmission
1
on RT-Alarm only
2
on RT-Alarm and RT-Fault
Function: Flashing mode of the two LED Alarm
3
alternating while V1/V2 run
4
simultaneously on unacknowledged alarms
Function: LED system part disabled on mode manned
5
off in mode manned
6
on in mode manned
Function: Resound or not on new alarm
7
Resound sounders on new alarm
8
No resound on new alarm
Option
Setting
Function: Activation mode of control lines 1-6
1
continuous on Alarm 1 and 2
2
continuous on Alarm 1
pulsating on Alarm 2
3
pulsating on Alarm 1
continuous on Alarm 2
4
pulsating on Alarm 1 and 2
5
continuous on Alarm 1
not activated with Alarm 2
6
pulsating on Alarm 1
not activated with Alarm 2
7
not activated with Alarm 1
continuous on Alarm 2
8
not activated with Alarm 1
pulsating on Alarm 2
9
don't use
10
don't use
11
continuous on RT-Alarm
same facility as RT-Alarm
–
12
continuous on Alarm 1 and 2
same facility as driver output (fire con-
–
trols)
13
continuous on Alarm 2
–
same facility as driver output (fire con-
trols)
14
continuous on RT-Fault
same facility as RT-Fault (until inactive)
–
possible with control line 6 only
–
Option 1 to 13 active until Reset
Key
LED zone 1 - x
Red
Zone 1 - x
Default off
on
on
Key
LED zone 1
LED zone 2
Red
yellow
Red
zone 1
Default
off
on
zone 1
Default
off
on
zone 2
off
Default
on
Zone 2
+ key 2
Key
LED zone 1 – 6
Red
Default off
zone 1 = control line 1
on
zone 2 = control line 2
zone 3 = control line 3
slow
zone 4 = control line 4
zone 5 = control line 5
fast
zone 6 = control line 6
on
control lines 3 – 6 with
slow
8/12 zone panel only and
additional control card
on
slow
on
fast
fast
A6V10265083_a_en_--
Configuration
yellow
on
on
yellow
Default
off
on
yellow
on
on
slow
slow
fast
on
on
slow
fast
fast
35