S7 Communication; Directly Accessing A Sinamics G120 Converter From A Simatic Panel - Siemens SINAMICS G110M Function Manual

Fieldbus systems
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

3.5

S7 communication

Communication via the S7 protocol facilitates the following:
● Access to the inverter with Startdrive.
● Remote maintenance of the inverter with Startdrive across network boundaries.
(https://support.industry.siemens.com/cs/ww/en/view/97550333)
● Control of the inverter directly via SIMATIC Panels via PROFIBUS or PROFINET without
higher-level control.
Note
Number of S7 protocol connections
The inverter supports four S7 protocol connections. Two of these are required for Startdrive.
Each of the remaining two are available for access to the inverter via SIMATIC Panels.
3.5.1

Directly accessing a SINAMICS G120 converter from a SIMATIC panel

Example of direct access to the inverter via a SIMATIC panel
You want to use the SIMATIC panel to do the following:
● Switch the inverter on and off
● Enter a setpoint
● Display the actual value and status
Requirements
You have installed the following software packages on your computer and made the
following settings:
● WINCCflex 2008 SP1 or higher
● Startdrive
● You have configured the inverter in Startdrive
● Inverter and panel are connected with one another via PROFIBUS or PROFINET.
● The same baud rates are set in the inverter and in the panel.
● The bus address configured in WinCC flexible matches the bus address of the inverter.
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Remote maintenance across network boundaries
Directly accessing a SINAMICS G120 converter from a SIMATIC panel (Page 55)
Communication via PROFIBUS and PROFINET
3.5 S7 communication
55