Siemens SINAMICS G110M Function Manual page 154

Fieldbus systems
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Communication via RS485
5.5 Communication via BACnet MS/TP - only CU230P-2 HVAC / BT
The inverter can simultaneously process up to 32 SubscribeCOV services. These can all
refer to the same object instances - or different object instances.
SubscribeCOV monitors the property changes of the following objects:
● Analog Input (AIxx),
● Analog Output (AOxx),
● Analog Value (AVxx),
● Binary Value (BVxx) and
● Multi-state Input (MSIxx)
Note
SubscribeCOV services are not retentive; i.e., when restarting the CU the master must
reinitiate SubscribeCOV services.
Code numbers of the object types supported in BACnet
Object type
Device Object
Binary Input Object
Binary Output Object
Binary Value Object
Analog Input Object
Object properties of the "Device" object type
Object_Identifier
Object_Name
Object_Type
System_Status
Vendor_Name
Vendor_Identifier
Model_Name
Firmware_Revision
Length = 480,
not supported
1)
2)
152
Code number for BACnet
object type
8
3
4
5
0
Application_Software_Version
Protocol_Version
Protocol_Revision
Protocol_Services_Supported
Protocol_Object_Types_Supported
Object_List
Max_APDU_Length_Accepted
Segmentation_Supported
Object type
Analog Output Object
Analog Value Object
Multi-State Input Object
Octet String Values
APDU_Timeout
Number_Of_APDU_Retries
Max Master
Max Info Frames
Device Address Binding
Database Revision
1)
2)
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Code number for BACnet
object type
1
2
13
47
Fieldbuses

Advertisement

Table of Contents
loading

Table of Contents