Communication via AS-i - only for G110M
7.3 Dual Slave mode
Default setting 31, slave 1 with profile 7.A.5: Control -> inverter
• AS-i.DO0
• AS-i.DO1
• AS-i.DO2
• AS-i.DO3
Default setting 31, slave 1 with profile 7.A.5: Inverter -> control
• p2080[4] = 722.2
• p2080[5] = 722.3
• Serial data transfer CTT2, four bytes cyclically or acyclically via PIV.
The reading and writing of parameters is possible via the PIV.
Because data is transferred bit-by-bit, the read and write process is
very slow.
• Time signal for the CTT2 transfer to the AS-i master
Default setting 34: Dual Slave mode with setpoint via AS-i field bus
The control accesses the two slaves of the inverter each via four bits.
Via slave 2, in accordance with profile 7.A.E, the control specifies the commands listed
below (AS-i.DO0 ... AS-i.DO2).
Via slave 1, the control sends the command for quick stop and the data in cyclical or
acyclical mode.
The control requires one bit per slave in order to specify the slave.
Default setting 34, slave 2 with profile 7.A.E: Control -> inverter
• AS-i.DO0
• AS-i.DO1
• AS-i.DO2
• AS-i.DO3
If the control specifies the speed setpoint, the inverter replies:
Default setting 34, slave 2 with profile 7.A.E: Inverter -> control
• p2080[0] = 53.13
• p2080[1] = 899.11 Pulses enabled
• p2080[2] = 722.0
• p2080[3] = 722.1
222
->
Time signal for the CTT2 transfer from the AS-i master
->
Data bit for the CTT2 transfer, four bytes cyclically or acyclically via
PIV. The reading and writing of parameters is possible via the PIV.
Because data is transferred bit-by-bit, the read and write process is
very slow.
->
p0881 = 2093.4
->
Select slave A or slave B, interconnected internally
State DI2
State DI3
->
ON / OFF 1
->
OFF 2
->
Acknowledge fault
->
Select slave A or slave B, interconnected internally
PLC ready to switch on
State DI0
State DI1
Override quick stop
->
->
->
->
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
->
AS-i.DI0
->
AS-i.DI1
->
AS-i.DI2
->
AS-i.DI3
AS-i.DI0
AS-i.DI1
AS-i.DI2
AS-i.DI3
Fieldbuses