What Do You Have To Set For Communication Via Profibus - Siemens SINAMICS G110M Function Manual

Fieldbus systems
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

3.7.2

What do you have to set for communication via PROFIBUS?

Configuring PROFIBUS communication
You require the appropriate engineering system to configure PROFIBUS communication in
the PROFIBUS master.
If required, load the GSD file of the inverter into the engineering system.
Setting the address
Set the address of the PROFIBUS slave.
Setting the telegram
Set the telegram in the inverter as in the PROFIBUS master. Interconnect the telegrams in
the control program of the PROFIBUS master with the signals of your choosing.
Application examples
You can find application examples for PROFIBUS communication on the Internet:
via PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
(https://support.industry.siemens.com/cs/ww/en/view/60441457)
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
(https://support.industry.siemens.com/cs/ww/en/view/78788716)
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Configuring communication to the control system (Page 76)
Setting the address (Page 78)
PROFIDRIVE profile - Cyclic communication (Page 17)
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F
Controlling the speed of a SINAMICS G110M / G120 (Startdrive) with S7-1500 (TO) via
Communication via PROFIBUS and PROFINET
3.7 Communication via PROFIBUS