Siemens SINAMICS G110M Function Manual page 145

Fieldbus systems
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Table 5- 29
Start parameter request: Writing the parameter value of p1121 from slave number 17
Value
Byte
Description
11 h
0
Slave address
06 h
1
Function code (write)
0258 h
2,3
Register start address
0007 h
4,5
Number of registers to be written to (40601 ... 40610)
0010 h
6,7
Number of registers
xx h
8
CRC "Low"
xx h
9
CRC "High"
Table 5- 30
Response for successful write operation
Value
Byte
Description
11 h
0
Slave address
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
06 h
1
Function code (write)
20 h
2
0002 h
3,4
40601: DS47 Control = 2 (request was executed)
2F04 h
5,6
40602: Function code 2F h (47), response length 4 bytes
8002 h
7,8
40603: Request reference mirrored = 80 h,
response identifier = 2 (change parameter)
0101 h
9,10
40604: DO-ID = 1, number of parameters = 1
xx h
11
CRC "Low"
xx h
12
CRC "High"
Table 5- 31
Response for unsuccessful write operation - write request still not completed
Value
Byte
Description
11 h
0
Slave address
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
06 h
1
Function code (write)
20 h
2
0001 h
3,4
40601: DS47 Control = 1 (request is processed)
2F00 h
5,6
40602: Function 2F h(47), response length 0 (fault)
0004 h
7,8
40603: Error code:
issued)
xx h
9
CRC "Low"
xx h
10
CRC "High"
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
0004 Response Not Ready (response has still not been
Communication via RS485
5.4 Communication using Modbus RTU
143