Baud Rates And Mapping Tables - Siemens SINAMICS G110M Function Manual

Fieldbus systems
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

5.4.3

Baud rates and mapping tables

Permissible baud rates and telegram delay
The Modbus RTU telegram requires pauses for the following situations:
● for the start identifier
● for separating the individual frames
● for the end identifier
Minimum duration: Processing time for 3.5 bytes (can be set via p2024[2]).
A character delay time is also permitted between the individual bytes of a frame. Maximum
duration: Processing time for 1.5 bytes (can be set via p2024[1]).
Table 5- 10
Baud rate in bit/s (p2020)
4800
9600
19200 (factory setting)
38400
57600
76800
93750
115200
187500
Note
The factory setting for p2024[1] and p2024[2] is 0. The inverter defines the particular values
depending on the protocol selection (p2030) or the baud rate.
Modbus register and Control Unit parameters
The inverter supports the subsequently listed registers. Error "Exception Code" is output if an
attempt is made to access other registers.
Note
Read and write access to inverter data
R: read via FC03; W: write via FC06; R/W: read via FC03 or write via FC06
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Baud rates, transmission times, and delays
Transmission time per
character (11 bits)
2.292 ms
1.146 ms
0.573 ms
0.286 ms
0.191 ms
0.143 ms
0.117 ms
0.095 ms
0.059 ms
Communication via RS485
5.4 Communication using Modbus RTU
Minimum pause be-
Maximum pause be-
tween two telegrams
tween two bytes
(p2024[2])
(p2024[1])
≥ 8.021 ms
≤ 3.438 ms
≥ 4.010 ms
≤ 1.719 ms
≥ 1.75 ms
≤ 0.859 ms
≥ 1.75 ms
≤ 0.75 ms
≥ 1.75 ms
≤ 0.556 ms
≥ 1.75 ms
≤ 0.417 ms
≥ 1.75 ms
≤ 0.341 ms
≥ 1.75 ms
≤ 0.278 ms
≥ 1.75 ms
≤ 0.171 ms
131