Sdo Services; Access To Sinamics Parameters Via Sdo - Siemens SINAMICS G110M Function Manual

Fieldbus systems
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

6.2

SDO services

You can access the object directory of the connected drive unit using the SDO services. An
SDO connection is a peer-to-peer coupling between an SDO client and a server.
The drive unit with its object directory is an SDO server.
The identifiers for the SDO channel of a drive unit are defined according to CANopen as
follows.
Receiving:
Transmitting:
Properties
The SDOs have the following properties:
● An SDO connection exists only in the Pre-Operational and Operational states
● Transmission is confirmed
● Asynchronous transmission (matches the acyclical communication via PROFIBUS DB)
● Transmission of values > 4 bytes (normal transfer)
● Transmission of values ≤ 4 bytes (expedited transfer)
● All drive unit parameters can be addressed via SDO
6.2.1

Access to SINAMICS parameters via SDO

You access SINAMICS parameters using the SDO service. To do this, you use objects 2000
hex ... 470F hex of the manufacturer-specific area of the object directory.
Because you cannot directly address all of the parameters using this area, you require for an
SDO job always the parameter number itself and the offset dependent on the parameter
number.
Selection of parameter range and the associated offset
Parameter range
0 < parameter number < 10000
10000 ≤ parameter number < 20000
20000 ≤ parameter number < 20000
30000 ≤ parameter number < 20000
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Server ⇐ client:
Server ⇒ client:
Communication over CANopen
COB ID = 600 hex + node ID
COB ID = 580 hex + node ID
Offset
Offset value
p8630[2] = 0
0
p8630[2] = 1
10000
p8630[2] = 2
20000
p8630[2] = 3
30000
6.2 SDO services