Interlocking; General Control Test Mode; Design Description; Technical Data - ABB REM 543 Technical Reference Manual

Hide thumbs Also See for REM 543:
Table of Contents

Advertisement

ABB Network Partner
4.1.12.4.
4.2.
4.2.1.
Page 48
REM 543 Protection,
Monitoring and Control
Latched, blinking (example 2)
ACK
ON
ALARM
Off text
On text
Off colour for steady LED
09-24 12:40:00
On colour for blinking LED
Fig. 4.1.12.3.-1. Example of a latched alarm with blinking LEDs.

Interlocking

The interlocking LED text can be defined in the same manner as for the other alarm
channels. The colour of the interlocking LED is yellow and cannot be changed. The nor-
mal state of the LED is inactive (no light). Furthermore, the interlocking LED has two
special modes. The first mode, recognized by a steady yellow light, indicates that the
interlocking disabling control is in operation. The second mode, recognized by a blink-
ing red light, indicates that the interlocking is in by-pass mode (control test mode).

General control test mode

The machine terminal has a general control test mode that overrides all interlocking sig-
nals (parameter V2 on channel 2). Activation of the interlocking test mode activates the
interlocking enable signals of all control objects. Then all control actions are allowed
and the enable signals of the objects are not checked during the control of the object.
The interlocking LED is blinking red as long as the test mode is active.

Design description

Technical data

Table 1: Energizing inputs
Rated frequency
Current inputs
rated current
Thermal withstand
capability
dynamic current withstand, half-wave value
input impedance
Voltage inputs
rated voltage
voltage withstand, continuous
burden at rated voltage
Sensor inputs, max 8
voltage range RMS
voltage range peak
input impedance
input capacitance
Technical Reference Manual
On text
Off text
On color for steady led
Off colour for steady LED
50.0/60.0 Hz
continuously
for 1 s
Part 1, General
alarind1
1 A/5 A
1.5 A/4 A/20 A
20 A/100 A/500 A
50 A/250 A/1250 A
<750 mΩ/<100mΩ/
<20 mΩ
100 V/110 V/115 V/120 V
(parameterization)
2 x U
(240 V)
n
<0.5 VA
±9.4 V
±12 V
>4.7 MΩ
< 1 nF