Setting Guidelines; Test Mode Functionality Testmode; Identification; Application - ABB Relion 650 Series Applications Manual

Transformer protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 504 124-UEN B
parameters are available in the IED. Any of them can be activated through the different
programmable binary inputs by means of external or internal control signals.
18.3.3

Setting guidelines

The setting
group can also be selected with configured input to the function block ACTVGRP.
The parameter
between. Only the selected number of setting groups will be available in the Parameter Setting
tool (PST) for activation with the ACTVGRP function block.
18.4

Test mode functionality TESTMODE

18.4.1

Identification

Function description
Test mode functionality
18.4.2

Application

The protection and control IEDs have a complex configuration with many included functions.
To make the testing procedure easier, the IEDs include the feature that allows individual
blocking of a single-, several-, or all functions.
This means that it is possible to see when a function is activated or trips. It also enables the
user to follow the operation of several related functions to check correct functionality and to
check parts of the configuration, and so on.
18.4.3
Setting guidelines
Remember always that there are two possible ways to place the IED in the "Test mode: On"
state. If, the IED is set to normal operation (
being in the test mode, the input signal INPUT on the TESTMODE function block might be
activated in the configuration.
Forcing of binary output signals is only possible when the IED is in test mode.
18.5

Change lock CHNGLCK

18.5.1
Identification
Function description
Change lock function
Transformer protection RET650
Application manual
ActiveSetGrp , is used to select which parameter group to be active. The active
MaxNoSetGrp defines the maximum number of setting groups in use to switch
IEC 61850
identification
IEC 61850
identification
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 60617
identification
TESTMODE
-
TestMode = Off ), but the functions are still shown
IEC 60617
identification
CHNGLCK
-
Section 18
Basic IED functions
GUID-0411129B-3A42-4A3B-A8E7-178D0EA5A7EA v2
ANSI/IEEE C37.2
device number
-
GUID-6039E749-18CB-46C4-A4AD-3A8F09378522 v2
ANSI/IEEE C37.2
device number
-
M15259-3 v3
M11407-3 v4
M15260-3 v3
251