Appendix C-2 Differences of Buffer Memory

BFM No.
High
Low
order
order
16bit
16bit
-
#0
#2
#1
-
#3
#5
#4
-
#6
#8
#7
#10
#9
-
#11
-
#12
#14
#13
-
#15
-
#16
#18
#17
#20
#19
#22
#21
130
Item
Pulse rate
1 to 32,767 PLS/REV
Feed rate
1 to 2,147,483,647 (user unit)
b1, b0: System of units
b3, b2: Interrupt input setting
b5, b4: Position data multiplier
b6: Acceleration/deceleration mode
b7: Variable speed operation acceleration/
deceleration setting
b8: Pulse output format
Operation parameter
b9: Rotation direction
b10: Zero return direction
b11: Limit deceleration mode
b12: DOG input polarity
b13: Count start point
b14: STOP input polarity
b15: STOP input mode
1 to 2,147,483,647 (user unit)
Maximum speed
Set the value within 1 to 200,000 Hz when
converted to pulse data.
0 to 32,767 (user unit)
Bias speed
Set the value within 0 to 200,000 Hz when
converted to pulse data.
1 to 2,147,483,647 (user unit)
JOG speed
Set the value within 1 to 200,000 Hz when
converted to pulse data.
1 to 2,147,483,647 (user unit)
Zero return speed
Set the value within 1 to 200,000 Hz when
(high speed)
converted to pulse data.
1 to 32,767 (user unit)
Zero return speed
Set the value within 1 to 200,000 Hz when
(creep)
converted to pulse data.
Number
of
zero-point
0 to 32,767
signal for zero return
-2,147,483,648 to 2,147,483,647 (user
unit)
Zero-point address
Set the value within -2,147,483,648 to
2,147,483,647 PLS when converted to
pulse data.
Trapezoidal acceleration/deceleration:
1 to 32,767 ms
Acceleration/
Approximate
deceleration time
deceleration:
1 to 5,000 ms
Starting delay time
0 to 1,000 ms
-2,147,483,648 to 2,147,483,647 (user
unit)
Target address Ι
Set the value within -2,147,483,648 to
2,147,483,647 PLS when converted to
pulse data.
1 to 2,147,483,647 (user unit)
Operation speed Ι
Set the value within 1 to 200,000 Hz when
converted to pulse data.
-2,147,483,648 to 2,147,483,647 (user
unit)
Target address ΙΙ
Set the value within -2,147,483,648 to
2,147,483,647 PLS when converted to
pulse data.
Appendix C: Differences with FX2N-1PG
Appendix C-2 Differences of Buffer Memory
Setting range
FX
-1PG
3U
1 to 999,999 (user unit)
b3, b2: Not used
b6: Not used
b7: Not used
b11: Not used
1 to 153,000 (user unit)
Set the value within 10 to 100,000 Hz
when converted to pulse data.
0 to 15,300 (user unit)
Set the value within 0 to 10,000 Hz when
converted to pulse data.
1 to 153,000 (user unit)
Set the value within 10 to 100,000 Hz
when converted to pulse data.
1 to 153,000 (user unit)
Set the value within 10 to 100,000 Hz
when converted to pulse data.
1 to 15,300 (user unit)
Set the value within 0 to 10,000 Hz when
converted to pulse data.
-999,999 to 999,999 (user unit)
Set the value within -999,999 to 999,999
PLS when converted to pulse data.
Trapezoidal acceleration/deceleration:
S-shaped
acceleration/
50 to 5,000 ms
Not used
-999,999 to 999,999 (user unit)
Set the value within -999,999 to 999,999
PLS when converted to pulse data.
1 to 153,000 (user unit)
Set the value within 10 to 100,000 Hz
when converted to pulse data.
-999,999 to 999,999 (user unit)
Set the value within -999,999 to 999,999
PLS when converted to pulse data.
FX
-1PG