Mitsubishi Electric MELSEC-F Series User Manual page 48

Hide thumbs Also See for MELSEC-F Series:
Table of Contents

Advertisement

FX
-1PG User's Manual
3U
4. Program description example
In the program below, the operation speed is changed as follows.
Operation speed will be changed to 200,000 Hz if the current address exceeds K2,000.
Operation speed will be changed to 100,000 Hz if the current address exceeds K5,000.
M8000
RUN monitor
M20
READY
42
FNC233
D10
K2000
ANDD>
FNC233
D10
K5000
ANDD>
6 Before Starting Positioning Operation
6.6 Operation Speed Change Function
FNC 12
U0\G26
D10
DMOV
FNC 12
U0\G28
K4M20
MOV
FNC 12
U0\G60
D30
DMOV
FNC 12
K200000 U0\G55
DMOV
FNC 12
K100000 U0\G55
DMOV
END
Reading of current address
Reading of status information
Reading of current value of
operation speed
Changes the operation speed
to 200,000 Hz
Changes the operation speed
to 100,000 Hz