[BFM#56, #55] Operation speed change value

Set the operation speed change value that is used in the operation speed change function.
BFM No.
High order
Low order
16bit
16bit
#56
*1.
In case of external command positioning operation
-2,147,483,647 to -1, 1 to 2,147,483,647 (user unit). Set the value within -200,000 to -1, 1 to 200,000
Hz when converted to pulse data.
7.4.9
[BFM#57] Operation command ΙΙ
A list of operation command II is as shown in the following table.
BFM No.
High order
Low order
16bit
16bit
-
*1.
Timing of detection.
Level detection: activated when the bit is set or cleared.
Edge detection: activated at OFF-to-ON transition.
Point
If INT0 (b0) or INT1 (b1) is on when the positioning operation starts, it automatically turns off.
76
→ For details on the operation speed change function, refer to Section 6.6.
Setting range: 1 to 2,147,483,647 (user unit)
The value must be within the range from 1 to 200,000 Hz when converted to pulse
#55
*1
data.
Bit
Item
No.
b0
INT0
#57
b1
INT1
b2 to
-
b15
Description
Description
The interrupt input is executed via the PLC (BFM).
INT0 turns on when b0 = ON.
The interrupt input is executed via the PLC (BFM).
INT1 turns on when b1 = ON.
Not used
7 Buffer Memory
7.4 Control Data
R/W
Default
R/W
K0
*1
Default
Detection
Edge
H0000
Edge
-
-