Heating circuit control settings
The control settings for the heating circuits are explained below.
Parameters with numbers 2xxx
always relate to the first heating cir-
cuit (A1), whereas numbers 3xxx and
4xxx describe the identical para-
meters of the second (M2) and third
(M3) heating circuits.
A1
Direct heating circuit
M2
Mixer circuit 1 with di-
rectly controlled mixer
motor (230 V)
2000 Room t standard / 2001 Room t reduced
Presetting the set room temperature of the heating circuit for "Standard" and
"Reduced" operating modes.
The centre position of rotary selector
s (Reduced: m) specifies the tem-
perature preset here at the control
unit. This value applies to all circuits
without remote control.
With rotary selector s (Reduced: m),
the temperatures can be matched in
steps of 1 °C by ±5 °C, without chan-
ging the values set here.
Heating circuit control settings
M3
Mixer circuit 2 with KM
BUS mixer
Note
Parameters 3xxx and 4xxx are only
available if the associated heating cir-
cuits are components of the system
diagram.
2xxx
3xxx
Note
With the set room temperature
selected at rotary selector s
(Reduced: m), the control unit calcu-
lates the set flow temperature in
weather-compensated mode for the
heating circuit in accordance with the
set heating curve. The set flow tem-
perature for room temperature-depen-
dent control is calculated from the
differential of the set and actual room
temperature.
The maximum value for "Room t
reduced" is "Room t standard" -1 K.
Menu
&
"Device settings"
&
"Programming"
&
"Heating circuits"
&
"Room t standard" or "Room t
reduced"
4xxx