P13 - Limit Thresholds - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

Parameterization
9.3 Parameters
9.3.13

P13 - Limit thresholds

This menu is divided into 4 sections for the limit thresholds LIM1 ... 4.
You can find more information on the user limits in chapter User limit threshold LIMx
(Page 57).
P13
Designation on
ATC display
User limit
thresholds
(LIMn, n =
1...4)
P13.n.01
Reference meas-
urement
P13.n.02
Reference source
P13.n.03
Channel number
P13.n.04
Function
P13.n.05
Upper threshold
P13.n.06
Multiplier
P13.n.07
Delay
P13.n.08
Lower threshold
P13.n.09
Multiplier
P13.n.10
Delay
140
Description
Reference measurement
- Defines which measurements of the ATC6300
the limit threshold is applied to. For the list of
reference measurements, refer to chapter User
limit threshold LIMx. (Page 57)
Source of reference measurement
– If the reference measurement involves an
electrical measurement, this parameter speci-
fies whether it refers to Line 1 or Line 2.
No. channel No. (x)
– If the reference measurement is an internal
multi-channel measurement, the channel num-
ber is defined here.
Function
– Defines the mode of operation of the limit
threshold (see chapter User limit threshold
LIMx (Page 57))
Upper threshold
– Defines the upper threshold obtained by mul-
tiplying the value of P13.n.06 by the value of
P13.n.05.
Multiplier
- see Parameter 13.05
Delay
– Upper threshold intervention delay.
Lower threshold
– As above, but relating to the lower threshold.
Multiplier
- see Parameter 13.08
Delay
- see Parameter 13.08
Unit
Default
Range
OFF
OFF-
(List of meas-
urements) ....
OFF
OFF
Line 1
Line 2
1
OFF / 1 ... 99
Max
Max
Min
Min + Max
0
-9999 - +9999
x1
/100 – x10k
s
0
0.0 – 600.0
0
-9999 - +9999
x1
/100 – x10k
s
0
0.0 – 600.0
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents