Designation And Description Of The Outputs; Digital Outputs Outx - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

Operation

8.3 Designation and description of the outputs

Function
Key AUT simulation
Automatic test inhibition
LED test
Close Breaker 1 (BRK 1)
Open Breaker 1 (BRK 1)
Toggle Breaker 1 (BRK 1)
Close Breaker 2 (BRK 2)
Open Breaker 2 (BRK 2)
Toggle Breaker 2 (BRK 2)
Auxiliary voltage ready
Revision
8.3
Designation and description of the outputs
8.3.1

Digital outputs OUTx

The ATC6300 has 7 permanently integrated digital outputs which are designated as OUTx.
Designation
OUTx
The function of the integrated digital outputs can be freely parameterized by the user:
110
Description
Digital output
Description
Closing the input is the equivalent of pressing the
AUT key. The operating mode is changed ac-
cordingly.
Inhibits the automation test.
Makes all the LEDs on the front panel flash.
In the manual mode this function closes the
Breaker 1.
In the manual mode this function opens the
Breaker 1.
In the manual mode this function toggles the
status of Breaker 1.
In the manual mode this function closes the
Breaker 2.
In the manual mode this function opens the
Breaker 2.
In the manual mode this function toggles the
status of Breaker 2.
If this NC contact is open, alarm A18 is triggered.
If enabled, this function causes the following
reactions during revision of the system:
switch to OFF mode
disabling of feedback alarms A03-A04
enabling of any undervoltage release
Mounted on the device
1 - 7
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
Maximum number with
expansion modules
8 - 15