Siemens SENTRON ATC6300 Manual page 135

Table of Contents

Advertisement

P07 Pa-
Designation on ATC
rameter
display
Line 2
P07.09
Phase failure thresh Threshold limit for phase failure
P07.10
Phase failure delay
P07.11
Max. asymmetry
limit
P07.12
Max asymmetry
delay
P07.13
Max frequency limit
P07.14
Max frequency
delay
P07.15
Min frequency limit
P07.16
Min frequency delay Delay time for minimum frequency
P07.17
Line cont. OFF
mode
P07.18
Line cont. MAN
mode
P07.19
Generator start
delay
P07.20
Cooling time
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
Description
Delay time for the phase failure threshold limit
Maximum limit for asymmetry of the phases
Delay time for maximum asymmetry of the
phases
Limit for the maximum frequency
Delay time for the maximum frequency
Limit for minimum frequency
Setting of the voltage measurement in the OFF
mode
Line 2 control in MAN mode
Delay of generator start after failure of Line 2
Generator cooling time
Parameterization
9.3 Parameters
Unit
Default
Range
%
70
60 – 80
OFF
s
0.1
0.1 s - 30 s
%
15
1 % -
20 % / OFF
s
5
0.1 - 900
%
105
100 -
120 / OFF
s
3
0 - 600
%
95
OFF / 80 - 100
s
5
0 - 600
OFF
OFF
ON
OFF+GLOB
ON+GLOB
OFF
OFF
ON
OFF+GLOB
ON+GLOB
s
OFF
OFF / 1 - 6000
s
120
133