Technical Specifications - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

12.1.2.1

Technical specifications

Power supply
Supply voltage
Current consumption (max.)
Power loss (max.)
SSR output
Output type
Solid state output rating (at 60°C)
Contact type
Connecting terminals
Cable cross-section (min-max)
Tightening torque
Insulation
Impulse withstand voltage U
Operating frequency impulse withstand voltage
Ambient conditions
Operating temperature
Storage temperature
Relative humidity
Maximum degree of pollution
Overvoltage category
Altitude of environment (max.)
Enclosure
Enclosure material
Degree of protection
Weight
Certifications and approvals
The following standards are complied with:
Complies with standards
UL marking
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
imp
12.1 Expansion modules
5 V DC (supplied through the ATC6300)
20 mA
0.1 W
Solid state relays (Opto-Mosfet)
Max. 55 mA at 40 V DC / 30 V AC
4 NO contacts
Removable / plug-in
0.2 ... 1.5 mm
(AWG 28 ... 14)
2
0.18 Nm (1.7 lbf-in)
7.3 kV
4 kV
-20 ... +60 °C
-30 ... +80 °C
< 80 % (IEC / EN 60068-2-70)
2
3
≤ 2000 m
Polyamide RAL7035
IP20
54 g
cULus
IEC / EN 61010-1
IEC / EN 61000-6-2
IEC / EN 61000-6-3
UL 508
CSA C22.2-N°14
Four solid state outputs:
30 V AC, 55 mA general use
40 V AC, 55 mA general use
Use 60° C / 75 °C copper (CU) conductor only
AWG Range: 28 - 14 AWG stranded or solid
Field wiring terminals tightening torque:
1.7 lbf-in
Accessories
181

Hide quick links:

Advertisement

Table of Contents
loading