Advertisement

Connection
7.3 Connection of Siemens SENTRON switching devices
Operating times of the 3WT
Contact transfer time, off-
time*
Time I-O, time II-O
Time I-O-II (for min parame-
ter)*
* Comprises the minimum delay time from Line I to Line II of 100 ms (see parameter P05.03) in the OFF position
Note
Observe the specifications of IEC 60947-6-1 when planning transfer switching equipment.
88
Unit
ms
ms
ms
2x 3WT FSI
180
80
260
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
2x 3WT FSII
180
80
260